Product details
Key Features
- Output Channels: 4 output channels referenced to a single supply.
- Output Capacity: Voltage of 11V at 45mA current.
- Functional Data: Outputs de-energized state on failure.
- Response Time: 1ms (for all channels).
- Switching Frequency: 10kHz.
- Fault Detection: Configurable delay for module faults, with lead breakage and short-circuit detection.
- Fault Indication: Alarm signal via backplane bus with flashing red LED for each fault.
- Latch Mode: Configurable across all channels.
- Power Consumption: One power supply unit load; power dissipation of 5W.
- Galvanic Isolation: Isolated output from the backplane and power supply.
Technical Specifications
- Voltage (V): 11V (at 45mA current).
- Intrinsically Safe Output: Europe: II (1) 2G EEx ia/ib IIB/IIC T4.
- Permissible Field Circuit Values:
- Uo = 27.4V, Io = 110mA.
- Inductance (Lo): 8mH max (EEx ia IIB), 2mH max (EEx ia IIC).
- Capacitance (Co): 677nF max (EEx ia IIB), 87nF max (EEx ia IIC).
- Operating Temperature: -20°C to 70°C (-4°F to 158°F).
- Storage Temperature: -20°C to 100°C (-4°F to 212°F).
- Humidity: Max 95%, non-condensing.
- Vibration Resistance: 2g @ 10Hz to 500Hz, in accordance with IEC 68-2-6.
- Shock Resistance: 15g peak, 11ms duration.
- Protection Class: IP20 (requires additional housing for outdoor installation with at least IP54 rating).
Dimensions
- Size: 76mm (H) x 94mm (W) x 46mm (D) or 3.0” x 3.7” x 1.8”.
- Weight: 0.282 kg (0.62 lb).
FAQ
- What is the switching frequency of the TC-POB041?
- The switching frequency is 10kHz, suitable for rapid control in automation processes.
- Is the TC-POB041 suitable for hazardous areas?
- Yes, it is intrinsically safe and certified for use in Ex-rated zones (EEx ia/ib IIB/IIC T4).
- What types of faults does this module detect?
- The TC-POB041 detects lead breakage, short circuits, and other output faults, with an alarm indication.
For more detailed information, please check official datasheet: C200-introduction