Product details
Overview
The Honeywell MC-TSIM12 Serial Interface FTA is designed for seamless communication between Modbus-compatible devices and Honeywell control systems. This versatile module supports both EIA-232D and EIA-485D physical interfaces, ensuring compatibility with a wide range of multivendor Modbus devices. With robust performance and advanced error protection features, the MC-TSIM12 is ideal for industrial automation applications requiring reliable and efficient data exchange.
Key Features
- Flexible Communication Protocol
- Supports Modbus RTU protocol.
- Operates in both RS232D and RS485D modes.
- Enhanced Compatibility
- Qualified for multivendor Modbus-compatible devices.
- Configurable baud rates (1200ā19200 bps) and parity settings.
- Physical Interfaces
- EIA-232D: Supports lines such as TXD, RXD, RTS, CTS, and more.
- EIA-485D: Differential pair support with up to 15 device drops over 1.2 km.
- Data Handling Capabilities
- Organizes data into arrays, supporting up to 16 points per serial channel.
- Handles diverse formats: Boolean, Real, ASCII Strings, and Signed Integers.
- Robust Design
- ESD protection compliant with IEC 801.2.
- Surge withstand capability per IEEE SWC 472-1974.
- Power Efficiency
- Low power dissipation at 1.4 watts maximum.
- Extended Applications
- Industrial automation systems requiring serial asynchronous communication.
- Long-distance data exchange up to 1.2 km for RS485D.
Technical Specifications
Attribute | Specification |
---|---|
Brand | Honeywell |
Model | MC-TSIM12 |
Communication Protocol | Modbus RTU |
Physical Interfaces | EIA-232D / EIA-485D |
Baud Rates | Selectable: 1200, 2400, 4800, 9600, 19200 bps |
Data Quantity | Up to 16 points per serial channel, supporting multiple data formats |
Distance (FTA to Device) | RS232D: 15 m; RS485D: 1.2 km |
Power Dissipation | 1.4 W max |
Devices Supported | Up to 15 devices per FTA; 2 FTAs per SI IOM |
Applications
- Integration of Honeywell systems with Modbus-compatible field devices.
- Distributed control systems in industrial automation environments.
- Data acquisition from multiple remote devices over long distances.
For more detailed information, please check official datasheet: C200-introduction
There are no reviews yet.