Product details
Overview
The TC-HAO081 and TK-HAO081 modules are 8-point HART-analog output modules designed for precision and reliability. These modules deliver versatile current and voltage outputs, making them suitable for industrial control systems requiring HART and non-HART communication. Compatible with Honeywell’s control platforms, they ensure seamless integration and performance.
Technical Specifications
- Model: TC-HAO081, TK-HAO081
- Output Channels: 8 outputs
- Output Ranges:
- Non-HART: Ā±10.4V, 0ā10.25V, 0ā21mA
- HART: Current-only, 4ā20mA
- Resolution:
- Voltage: 16 bits (323 ĀµV/bit)
- Current: 15 bits (656 nA/bit)
- Scan Time: 10ms for all 8 channels
- Drive Capability: 2000 ā¦ (Voltage); 50ā750 ā¦ (Current)
- Accuracy:
- Voltage: Ā±0.1% of range
- Current: Ā±0.15% of range
- Temperature Drift:
- Offset Drift: 50 ĀµV/Ā°C (Voltage), 200 nA/Ā°C (Current)
- Gain Drift: 20 ppm/Ā°C (Voltage), 30 ppm/Ā°C (Current)
- Power Dissipation: 6.3W max
- Isolation Voltage: 2550VDC for 1 second
- Open Loop Detection: Less than 5 seconds for current outputs above 0.1mA
- HART Wiring Mode: Point-to-point only
- Connection: TC-TBNH 20-position terminal block
Applications
- Industrial process control systems
- Integration with Honeywell control platforms
- Systems requiring precise analog signal output
- HART-enabled communication for enhanced diagnostics
FAQ
Q: Is multi-drop mode supported for HART?
A: No, only point-to-point wiring mode is supported.
Q: What is the calibration interval?
A: The typical calibration interval is 12 months.
Q: Can this module detect open-loop currents?
A: Yes, it can detect open-loop currents with a typical detection time of under 5 seconds.
Q: What is the maximum isolation voltage?
A: The module is tested for 2550VDC for 1 second.
For more detailed information, please check official datasheet: C200-introduction
There are no reviews yet.