Overview
The TC-ODX081 diagnostic discrete output module provides reliable and robust performance for industrial automation systems, supporting 8 output points with advanced diagnostics for overload, no-load detection, and output verification. It operates efficiently across a voltage range of 74-132 VAC, making it suitable for a wide array of control applications.
Technical Specifications
Parameter | Specification |
---|---|
Brand/Model | TC-ODX081 Diagnostic Output Module |
Voltage Range | 74-132 VAC, 47-63 Hz |
Output Current Rating | 1 A max @ 30°C; 0.5 A max @ 60°C per point |
Surge Current | 8 A for 50 ms @ 30°C, 5 A for 50 ms @ 60°C |
On-State Current (Min) | 10 mA per output |
Off-State Leakage | 3 mA max per point |
Power Dissipation | 13.8 watts |
Output Signal Delay | Off-to-On/On-to-Off: 9.3 ms @ 60 Hz |
Inhibit Voltage | Max 25 V peak |
Isolation Voltage | 2546 VDC for 1s (channel to channel/user to system) |
Connection | Compatible with TC-TBNH 20-position terminal block |
FAQ
Q1: What is the maximum power dissipation of the TC-ODX081 module?
A: The module dissipates up to 13.8 watts under maximum load conditions.
Q2: What type of terminal block is compatible with the TC-ODX081 module?
A: The module works with the TC-TBNH 20-position terminal block.
Q3: What does the “ODX081” in the model number signify?
A: “ODX” indicates the module is an output diagnostic unit, and “081” refers to its 8-point design with 1 A max output per point.
Q4: Can the module handle high surge currents?
A: Yes, it supports a surge current of 8 A for 50 ms at 30°C.
Q5: What diagnostic functions are integrated into the module?
A: Overload/short trip detection, no-load monitoring, and output verification are standard.
For more detailed information, please check official datasheet: C200-introduction