Product details
Overview
The TC-PIL081 is an advanced Temperature Input Module with 8 channels designed for use with thermocouples and RTDs. It provides precise measurements with a configurable input type, ensuring flexibility for various industrial applications. With intrinsic safety certification (II (1) 2G EEx ia/ib IIB/IIC T4), it is ideal for hazardous environments. The module supports multiple temperature formats (Celsius, Fahrenheit, Kelvin) and offers high-accuracy thermocouple and RTD data with a fast response time of 4ms.
Features
- 8 Input Channels: Configurable for thermocouples and RTDs, grouped into two sets (0-3 and 4-7).
- Thermocouple and RTD Support: Measures a wide range of thermocouples (B, J, K, N, R, S, T) and RTDs (Pt100, Pt200, Ni100, Ni200, etc.).
- Intrinsically Safe: Certified for use in hazardous environments (II (1) 2G EEx ia/ib IIB/IIC T4).
- Cold Junction Compensation: Automatic compensation with high accuracy (+/- 0.8°C).
- RTD Sensor Modes: 2-wire, 3-wire, and 4-wire measurement with lead resistance compensation.
- Temperature Format: Configurable as Celsius, Fahrenheit, or Kelvin for all channels.
- High Accuracy: +/- 0.5% for thermocouples (E, J, K, N), and up to 0.1% for RTDs.
- Response Time: 4ms for fast temperature readings.
Technical Specifications
- Brand: TC-PIL081
- Model: Temperature Input Module
- Suffix Meaning: “081” indicates 8 input channels.
- Intrinsic Safety Certification: II (1) 2G EEx ia/ib IIB/IIC T4 (CENELEC)
- Temperature Input: Thermocouple (–270°C to 1768°C) and RTD (–200°C to 870°C).
- Accuracy: Thermocouples: +/- 0.5% (E, J, K, N); RTDs: 0.1% of span (maximum).
- Linearization Accuracy: +/- 0.2°C maximum.
- Cold Junction Compensation Accuracy: +/- 0.8°C at 25°C.
- Cold Junction Drift: 300ppm/°C (–20°C to –15°C), 100ppm/°C (–15°C to 70°C).
- Response Time: 4ms
- Resolution: 16 Bits
For more detailed information, please check official datasheet: C200-introduction
There are no reviews yet.